Abstract
The transformer losses can usually be classified into two basic categories: losses in the transformer core (voltage-dependent losses) and losses in the transformer winding copper (current-dependent losses). By increasing the number of active transformers in the transformer substation the authors reduce the total losses in the transformer copper but on the other hand increase the total losses in the transformer iron core. Considering this, it can be concluded that it is possible to determine the optimum number of active transformers in the substation for each operating condition together with the way they are connected. In this study, the authors propose a novel optimisation algorithm which can be used to determine the optimal operating conditions of the transformer substation to minimise annual energy losses while avoiding frequent transformer switching and assuring provision of sufficient transformation power in order to supply distribution load. The algorithms which are outlined are applicable for substations 110/xkV and 35/10(20)kV which have more than one transformer installed with different levels of substation topology complexity (flexibility).
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.