Air distributors are a typical kind of ventilation terminal that are widely used in air-conditioning systems. However, the high flow resistance of traditional air distributors leads to huge energy losses and poor indoor thermal comfort. Therefore, this paper uses experimental and numerical methods to examine the influence of key structural parameters on the resistance coefficient of air distributors. First, a resistance-coefficient test is carried out, and based on the test results a computational fluid dynamics model is developed. Second, a Taguchi design table is created and numerical simulation data are collected. Finally, the prediction results of Mean Response and Assisted Regression are compared. The resistance coefficient of prediction combination of Assisted Regression model is lower, so the optimal scheme is as follows: d = 90 mm, D = 155.5 mm, and h = 96.5 mm. The predicted resistance coefficient is 1.503, and the difference between the predicted and simulation results accords with the 95% confidence interval. These findings show that numerical simulation and the analysis method based on the orthogonal design presented in this paper enable the optimal design of an air distributor.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.