Abstract

This paper describes an allocation methodology for capacitor placement in unbalanced distribution systems to achieve loss minimization with an adequate voltage profile. Switched capacitor banks and/or fixed banks can be allocated on a per-phase or multi-phase, discrete basis, and this allows consideration of the actual unbalanced characteristics of distribution systems. While most methods available in the literature address some specific network loading conditions, e.g. average, light-load or heavy-load, the proposed algorithm is based on the daily load variation curve. The method consists of two main steps: (i) reactive power demand calculation to achieve loss minimization; (ii) discrete capacitor placement. The method is applied on the IEEE 4-bus, IEEE 123-bus and IEEE NEV Test Feeders as well as on an 85-bus feeder. Several alternative allocations are calculated and comparisons with results available in the literature are presented.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call