Abstract

Many of the power cuts in the electricity system in the last decade indicate that there is much work to be done to address the voltage instability and subsequent collapse. This study presents a method to find and select the optimum location of FACTs device using the hybrid line stability index (HLSI) that is appropriate for the prediction voltage collapse in power system networks. Such the HLSI was obtained by deriving expressions basics equivalent Line Stability Index (Lmn), and Fast Voltage Stability Index (FVSI) and mix theirs through a switch logic based on the voltage angle difference Where indicate the nearness voltage collapse. The HLSI has tested in Iraqi National Super Grid System (INSGS) it gives the same results as the other indicators (Lmn & FVSI). For the base state, INSGS was found to be stable with all the three indicators have approximately equal values least than 1 for all lines. The contingency state detects that ranks of bus 24 the weakest bus in the system with the lower maximum allowable reactive load of (490.371 Mvar) and the line critical concerning bus 24, the line connecting bus 20 to bus 24. The values the three indicators, Lmn, FVSI, and HSLI, approximately equal, increasing the accuracy of HLSI.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.