Abstract

This paper describes the development and testing of a digital gain switching governor for hydrogenerators. Optimal gains were found at different load points by minimizing a quadratic performance criterion prior to controller operating. During operation, the gain sets are switched in depending on the gate position and speed error magnitude. With gain switching operating, the digital governor was shown to have a substantial reduction of noise on the command signal and up to 42% faster responses to power requests. Non-linear control strategies enabled the digital governor to have a 2.5% to 2% reduction in speed overshoot on startups, and an 8% to 1% reduction in undershoot on load rejections as compared to the analog.