Abstract
The rapid response feature of SVC can improve the steady state stability (or small signal stability) of power system, if it is located appropriately. In this paper, an index for identifying the location of SVC in large scale power system is proposed. The proposed index indicates modal controllability of the weak damping oscillatory modes. A multimachine linearized analysis for computation of the most dominant eigenvalues is done. Then, the most effective state variables on the given mode or eigenvalue are determined by participation factor analysis. The controllability of same state variable is calculated in all nodes of the network. The location index for each node is absolute value of controllability in same node. For evaluating the results, some computer simulations are done using MATLAB SIMULINK. The results demonstrate validity of proposed index.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.