Abstract
A new procedure for the design of the droop control for voltage source converters (VSC) in islanded microgrid is presented. The droop control is commonly used to achieve the power balance in power system. It consists in a simple proportional control and the selection of its gains are commonly based only on a power balance criteria. However, some values of the gains may cause poor damped responses and even the instability of the system. In this paper, it is proposed a new droop control based on the parametrization of the H ∞ controller which permits to decouple the stability problem from the power balance. The application of the new controller is illustrated by simulation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.