Abstract

In this study, optimal discharge conditions of sorption thermal battery (STB) are determined for stable supply of the building cooling load based on different load patterns. Parametric analysis is conducted to ascertain the influence of heat source temperature and the mass flow rate ratio between the solution and the heat transfer fluid on the performance of the STB. The maximum values of energy storage density (ESD) and coefficient of performance (COP) are estimated as 207.73 kWh/m3 and 0.74, respectively. The daily transient behaviors of STB are examined in detail, and the optimal solution charge and the solution flow rate are quantified based on the building types (residential, hospital, hotel, and office). For a building with an air conditioning floor area of 181.63 m2, the most suitable cooling load response is observed in the hotel scenario. The minimum deviated cooling output from the building load is 8.69%. Concurrently, COP and ESD are estimated of 0.69 and 101.99 kWh/m3. This paper demonstrates the cooling load responsiveness and optimal operating point of STB based on building load pattern. Additionally, a dimensionless number is defined to generate the discharge trend and enable to predict COP and ESD.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.