Abstract
This paper presents a new approach to the analysis of the transient overvoltage (TOV) generated during switching of vacuum circuit breaker (VCB). The new technique overlaps the merits of both Fast Fourier Transform (FFT) and Wavelet Transform (WT). The new approach was applied on a real case study of a pumping station of a wastewater treatment plant located at Abu Rawash, Egypt. The pumping station is driven by induction motors. Alternative transients program (ATP) is used to simulate the selected case study. The Referential Integrity between FFT and WT analyses (RI-FFT/WT) is employed to choose the RC snubber circuit parameters (R and C). The optimal snubber circuit parameters design was determined from the hybridization between genetic algorithm (GA) and RI-FFT/WT. It is evident from the simulation results that the new hybrid GA-FFT/WT approach succeeded in the selection of the most optimal RC-snubber circuits required for the mitigation of the TOV.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.