Abstract

This paper proposes a novel robust thyristor-controlled series compensator (TCSC) controller based on proportional integral derivative with filter (PIDF) and uses a new hybrid optimisation evolutionary programming sine cosine algorithm (EPSCA) to improve the power system’s angle stability. The problem of the PIDF-TCSC design is transformed into an optimisation problem based on performance indices, such as damping factor, damping ratio, and eigenvalues, where the multi-objective function is employed to obtain the optimal stabiliser parameters. To examine the robustness of PIDF-TCSC, it was tested on a single-machine infinite-bus power system under different operating conditions. The performance of the system with the PIDF-TCSC controller was compared with the simulation results, and the results obtained with the proposed EPSCA were compared with those obtained with SCA, moth flame optimisation, and EP-based PIDF-TCSC methods. Simulation results showed the effectiveness of EPSCA for the PIDF-TCSC design and the superior robust performance for the enhancement of power system stability compared with other techniques in different cases.