Abstract

Combining demand-controlled ventilation (DCV) and economizer control can achieve adequate and even better indoor air quality with minimum cooling/heating energy consumption in buildings. The control instability during the transition processes between different control modes is among the major difficulties faced when combining DCV control with economizer control in applications. The practical energy benefit is another concern when using free cooling in the subtropical climate like Hong Kong. A robust control strategy, using “freezing”, gain scheduling, I-term reset and feedback transition control for different transition processes, is developed addressing the instability problems. The energy benefit of using economizer control is evaluated by over one year's comparison tests on two air-handling units in a building.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.