AbstractThis study focuses on an evaluation of the subsurface ground temperature distribution during operation of a soil-borehole thermal energy storage (SBTES) system. The system consists of an array of five 9 m-deep geothermal heat exchangers, configured as a central heat exchanger surrounded by four other heat exchangers at a radial spacing of 2.5 m. In addition to monitoring the temperature of the fluid entering and exiting each heat exchanger, 5 thermistor strings were embedded in boreholes inside and outside of the array to monitor changes in ground temperature with depth. After 75 days of heat injection at a constant rate of 20 W/m, corresponding to 11.5 GJ of thermal energy, the average ground temperature in the array increased by 7°C. However, depending on the storage volume definition, only 2.43–4.86 GJ of thermal energy was stored attributable to heat losses. After a 4-month rest period the heat storage was observed to decrease by 60% owing to further heat losses. The trends in subsurface temp...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.