Abstract

The aim of the study was to investigate the influence of moderate temperatures on the efficiency of a full-scale anaerobic treatment system consisting of a primary sedimentation unit (PST) and an anaerobic baffled reactor (ABR, approx. 10m3 ). Therefore, two trials with different test setups in series were carried out (1st trial: continuous load; 2nd trial: diurnal variation load). The plant was fed with municipal wastewater and operated at temperatures between 8 and 24°C. The mean efficiency of the ABR was low, compared to the one of the PST. At 10°C, only 10% of the COD was removed. The COD (chemical oxygen demand) removal efficiency of the plant (PST+ABR) averaged 50%. At low temperatures, volatile fatty acids began to accumulate. In both trials, the contents of total suspended solids in the sludge bed differed distinctly and influenced the effort for desludging. PRACTITIONER POINTS: The operation of ABR in combined collection systems depends on the efficiency of the pretreatment unit. At cold temperatures, an ABR has no advantages compared to conventional pretreatment processes. For use under moderate conditions, the design must be adjusted.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.