Abstract

This paper deals with the impact of shunt-FACTS devices on the synchronous generator loss of excitation (LOE) protection. Considered shunt-FACTS devices in this paper include the static VAR compensator (SVC) and static synchronous compensator (STATCOM). The SVC has been modeled by thyristor switched capacitor (TSC) and thyristor controlled reactor (TCR) branches. Also, 48-pulsed converter is used to model STATCOM. The LOE relay considered in this paper is a negative offset mho distance relay containing two zones. It has been shown that injected reactive power of by shunt-FACTS devices prevents from the generator voltage drop during LOE, which causes the operation of LOE relay to be delayed. It has been also shown that when an incomplete LOE occurs, the presence of shunt-FACTS devices leads to under-reach of the relay. In this paper, various operational conditions of the power system and shunt-FACTS devices have been surveyed to authenticate the results.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.