Abstract

A model for radiant air conditioning with an infrared-transparent membrane has been developed to address the problems of the risk of condensation on the surface of the radiant cooling plate and the limitation of the cooling capacity by the indoor dew point temperature. The condensation and cooling characteristics of two types of radiant air conditioning were compared and analyzed by numerical simulation. The effects of different water supply temperatures, water supply velocities, and indoor relative humidities on the cooling and condensation characteristics of radiant air conditioning with an infrared-transparent membrane were investigated. For every 1 °C decrease in the water supply temperature, the cooling capacity increased by 8.92 W/m2 and the surface temperature of the infrared-transparent membrane decreased by 0.47 °C, and the water supply velocity was optimal. In addition, under indoor relative humidity conditions of less than 70 %, there was no condensation risk for radiant air conditioning.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.