Abstract

The paper presents the study on operation and performance of thermal energy storage (TES) system. The TES system is installed at a cogeneration plant for campus cooling. Operating data from 2006 until 2009 were anlaysed to evaluate the operating modes, half-cycle figure of merit (FOM) and thermocline performance of the TES system. The findings indicate that the TES system was operated based on partial mode strategy. The average half-cycle FOM evaluated for charging and discharging are 0.47 and 0.67 respectively. The thermocline thickness estimated is 1.5 m. The temperature distribution profiles indicate that the TES functioned as stratified TES.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.