Abstract

An open-circuit insulated-gate bipolar transistor fault detection technique for cascaded H-bridge (CHB) multilevel converters is presented in this paper. This technique, designed to be implemented independently for each CHB leg, utilizes one current sensor and one voltage sensor to monitor a leg's current and output voltage. Measured voltages are compared to expected voltages, and deviations are used to determine open-circuit fault locations based on the deviation's magnitude and current flow direction. Once potential fault locations have been identified, the fault location is systematically isolated and then verified, reducing the possibility of unnecessary corrective actions due to fault misidentification, e.g., an intermittent gate-misfiring fault being classified as an open-circuit fault. The proposed technique can be implemented for any number of cells, is independent of the pulse width modulation strategy used, and can be applied to symmetric and asymmetric CHB converters regardless of the cell input dc-source magnitudes utilized, i.e., cell input voltages are not required to be equal or to exist in specific ratios. For a CHB leg with $M$ cells, the proposed technique identifies and isolates open-circuit switch faults in less than $2M$ measurement (sampling) cycles, and verification is completed in less than one full fundamental cycle. Experimentally obtained data demonstrate the efficacy of the proposed fault detection and isolation technique.