Abstract
This paper first provides an in-depth analysis of open phase conditions in three phase power transformers. It describes why and how, upon loss of a single phase on the high or primary side of a transformer, voltages and currents on the low or secondary side greatly depend not only on the windings configuration but also sometimes on transformer's core construction as well. Some particular cases are discussed in which detecting a high side open phase is very difficult with current transformers (CT) only on the low side. Then after examination of the secondary voltages and currents practical and reliable algorithms are presented for identification and protection of high side open phase conditions from the low side of a power transformer. Digital simulation is used for verification of the analysis results and the protection algorithms.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.