Abstract

Introduction: Medical air (MA) is widely used in hospitals, often manufactured onsite by compressing external ambient air and supplied through a local network piping system. Onsite production gives rise to a risk of impurities that are governed by the same pharmacopoeia purity standards applicable to commercially produced MA. The question to be addressed in this paper is how to assess if a lack of purity poses a medical problem? Methods: The MA produced onsite at a major Canadian hospital was monitored for carbon dioxide (CO2) and other impurity gases at high frequency (one per minute) over a two-month period. Results: The average CO2 concentration was 255 ppm. The United States Pharmacopeia (USP) threshold of 500 ppm was exceeded during 1% of the total study period, and the average while exceeding the threshold was 526 ppm. The maximum concentration was 634 ppm. Discussion and conclusion: To our knowledge, there is only one study that evaluated the effects suffered by respiratory patients of elevated nitric oxide in MA; thus, it is not clear what are the medical bases for the thresholds stated in the USP. To perform a Quality Risk Assessment, the threshold and the time above threshold should be considered in determining the frequency of sampling and analysis, and operating methods required to ensure the quality of MA entering the pipeline meets the clinical, regulatory, and patient safety standards. In conclusion, because the USP does not provide impurity thresholds for specific patients nor time above thresholds, there is a need for the medical community to determine these quantities before it can be known if the purity of MA is a problem.

Highlights

  • Medical air (MA) is widely used in hospitals, often manufactured onsite by compressing external ambient air and supplied through a local network piping system

  • The United States Pharmacopeia (USP) threshold of 500 ppm was exceeded during 1% of the total study period (719 measurements), and the average while exceeding the threshold was 526 ppm

  • In this paper a dataset of CO2 concentration measurements in onsite produced MA indicates periodic breaches in the USP threshold. This is the first example of testing of onsite production of MA to appear in the peer reviewed literature

Read more

Summary

Introduction

Medical air (MA) is widely used in hospitals, often manufactured onsite by compressing external ambient air and supplied through a local network piping system. Onsite production gives rise to a risk of impurities that are governed by the same pharmacopoeia purity standards applicable to commercially produced MA. MA can be produced by external manufacturers, filled in cylinders and transported to the site of use This form of supply is directly regulated by the relevant country’s pharmacopeia [1]. For hospitals MA is most efficiently manufactured onsite by compressing external ambient air and supplied through a local network piping system. Onsite production gives rise to a risk of impurities that are governed by the same pharmacopoeia purity standards, and should be assessed. Of particular importance are dryers that consist of dual columns that operate on the principle of pressure swing adsorption, when one column swings to Edwards et al Multidisciplinary Respiratory Medicine (2018) 13:12 low pressure to dehumidify the absorbing material and the second takes over as the active dryer

Methods
Results
Conclusion
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call