Abstract
In this paper, three typical ground source heat pump (GSHP) projects applied to residential buildings in cold area in China are investigated. According to the on-site tested data, such as temperatures and flow rates of the circulating water on the user side and ground side and the power consumption, the operating performance of the whole system is evaluated. The results of the on-site test show that some equipment capacity of the residential GSHP systems investigated in this study was inappropriate in the actual operation conditions. The main problem of the systems is the improper design with “large flow rate and small temperature difference.” In general, the investigated systems are in an operation mode with high energy consumption, which means they have great energy-saving potential. In addition, compared with the systems applied to pure residential buildings, those employed in mixed residential and commercial buildings can efficiently reduce the thermal imbalance of the underground. Finally, some possible energy-saving retrofit measures have been suggested according to the results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.