Abstract

The arc extinguishing performances are the most important performance of the circuit breaker. However, there is still no methods of onsite detection and evaluation. The arcing time is an important indicator of the arc extinguishing performance of the circuit breaker, which can reflect the characteristic quantity of the arc extinguishing performance of the circuit breaker. This paper introduces an onsite detection method for arcing time of circuit breakers. The arcing time is detected by detecting electromagnetic waves radiated during the breaking process of the circuit breaker. The circuit breaker simulation platform was established in the laboratory, and the arc generated during the breaking process of the circuit breaker was recorded by the high-speed camera, and the electromagnetic wave radiated during the breaking process was measured by the antenna. Relationship of duration of radiated electromagnetic waves and arcing duration was analysed, the results show that they are very consistent. Therefore, this method can be used to realize the charging detection of the arcing time of the circuit breaker. This method was used to perform multiple tests on site and a defect was found.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.