Abstract

This paper presents a method for determining Thevenin's Equivalent (TE) for a node in a power system using local PMU measurements at that node. Three consecutive voltage and current measurements are used to determine the TE. The proposed method recognizes and considers the phase angle drift caused by the slip frequency between the PMU sampling frequency and the power system frequency. The accuracy of the proposed method has been verified through application to the IEEE 30 bus test system as well as to a real system data measured at the terminals of a wind farm. The proposed method is going to be used to determine an online TE, which will be used to monitor the system capability to accommodate the wind power by updating a capability chart of the system at the node where the wind farm is connected.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.