Abstract
Summary form only given. This paper proposes and evaluates a strategy to mitigate the transients of an apparatus, e.g., an electronically-interfaced distributed energy resource (DER) unit. This strategy is based on response monitoring and can be implemented based on either SPAA (set point automatic adjustment) or SPAACE (set point automatic adjustment-correction-enabled). SPAA takes advantage of an approximate model of the system to calculate the intermediate set points. SPAACE monitors the trajectory of the variable of interest and bases its decisions on the trend of variations of that variable and accounts for the inaccuracies and unmodeled dynamics by switching the command input between alternative set points. Case studies are presented to demonstrate the application and effectiveness of the proposed strategy in limiting voltage or current excursions in balanced and unbalanced microgrid study systems, subsequent to a step change in set point, load switching, and black start.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.