Abstract
We constructed an on-line partial discharge (PD) monitoring system (PDOM) with a CT sensor, an analogue-digital converter, and a tablet PC. A sampling frequency for data acquisition is 100 MHz, and we exchange on-site PD data through a cloud system. We successfully measured PDs in the early stage of insulation deterioration of a cross-linked polyethylene (XLPE) cable in a field site. Additionally, following PD detection by using a PDOM, we can locate a PD position by using a PD locator (PDL) system. By locating a PD, we can estimate the actual PD magnitude considering attenuation factor of a high frequency pulse. We show how the PDL system works on a XLPE cable network with time synchronization between two positions by using an injection current pulse. The locating accuracy of the PDL system is evaluated.