Abstract

This paper presents a novel rule-based method for online localization and phase selection of multiple partial discharge (PD) sources in cross-bonded cable (CBC) networks by simultaneous measurements of PD pulse trains at all link boxes. The proposed method detects PD defective cable sections (localization task) and their corresponding defective phases (phase selection task) regardless of the number of PD sources inside the CBC network and their severity differences. For the first time, the proposed method is capable of detecting more than one PD source by analysing PD pulse trains. Numerous simulations of different case studies performed in EMTPRV software indicate highly accurate performance of the proposed method even at high noise levels.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.