Abstract

<span lang="EN-US">In this paper we propose a strategy for real-time detection of interturn short-circuit faults (ISCF) on three-phase induction motor (IM) by using a Vold-Kalman filter (VKF) algorithm. ISCF produce a thermal stress into the stator winding due to large current that flows through the short-circuited turns. Therefore, incipient fault detection is required in order to avoid catastrophic failures such as phase to phase, or phase to ground faults. The strategy is based on an analytical IM model that includes a ISCF fault in any of the phase windings and considering the </span><em><span lang="EN-US">h<sup>-th</sup></span></em><span lang="EN-US"> harmonic in the voltage supply. Based on equivalent electrical circuits with harmonics in sequence components, we propose a strategy for detection of an ISCF on IM by tracking the 5<sup>th</sup> harmonic current component using a VKF algorithm. The proposed model is experimentally validated using a three-phase IM with modified stator windings to generate ISCF. Also, the IM is feeded by a programmable voltage source to synthesize distorted voltage supply with the 5<sup>th</sup> harmonic. The results demonstrated that the positive-sequence magnitude for the 5<sup>th</sup> harmonic current component is a good indicator of the fault severity once it exceeds a threshold limit value, even under load variations and unbalanced voltages.</span>