Abstract

Three-phase four-wire power cables are a primary kind of power transmission method in low-voltage distribution networks. This paper addresses the problem that calibration currents are not easily electrified during the transporting of three-phase four-wire power cable measurements, and proposes a method for obtaining the magnetic field strength distribution in the tangential direction around the cable, finally enabling online self-calibration. The simulation and experimental results show that this method can self-calibrate the sensor arrays and reconstruct the phase current waveforms in three-phase four-wire power cables without calibration currents, and this method is not affected by disturbances such as wire diameter, current amplitudes, and high-frequency harmonics. This study reduces the time and equipment costs required to calibrate the sensing module compared to related studies using calibration currents. This research offers the possibility of fusing sensing modules directly with running primary equipment, and the development of hand-held measurement devices.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.