Abstract
This paper presents a new procedure to track the disturbance source location of voltage sags and shunt capacitor switching transients in a power system based on branch current measurements. In the proposed method, the power-quality metering locations are first determined by the sensitivity of the system fault-current level to the fault voltage. Then, a current deviation index for representing the change of each measured branch current rms magnitudes before and after the disturbance is calculated to track the disturbance source location within an area confined by the directions of the top-priority branches. The IEEE 30-bus benchmark system and an actual transmission system with recorded power-quality disturbance events are used to illustrate the usefulness of the proposed method. Simulation results obtained by the proposed method are also compared with those obtained by a previously developed approach and by actual recorded data. By observing the results, it shows that the proposed method is efficient and accurate to track the source area of voltage sags or shunt capacitor switching transients.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.