Abstract

In this article, we consider a dynamic model of a three-phase power system including nonlinear generator dynamics, transmission line dynamics, and static nonlinear loads. We define a synchronous steady-state behavior which corresponds to the desired nominal operating point of a power system and obtain necessary and sufficient conditions on the control inputs, load model, and transmission network, under which the power system admits this steady-state behavior. We arrive at a separation between the steady-state conditions of the transmission network and generators, which allows us to recover the steady-state of the entire power system solely from a prescribed operating point of the transmission network. Moreover, we constructively obtain necessary and sufficient steady-state conditions based on network balance equations typically encountered in power flow analysis. Our analysis results in several necessary conditions that any power system control strategy needs to satisfy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.