Abstract
In an attempt to investigate the accuracy of predictions of fire-induced flow into a compartment by Fire Dynamics Simulator (FDS), a follow-up study was explored by comparing with the Steckler’s experimental data obtained at National Bureau of Standards in 1979. Improvements to the previous study include finer grids, an inclusion of radiative heat in the combustion model, and an increased computational domain. The burner location for the modeling scenarios of fire at corner or against wall are shifted to compensate for the reduced entrainment. The input and set-up changes made to the FDS simulation allowed significant improvements in the prediction of mass flow rates for all three positions of the fire source. However, there is not much improvement for the remaining three parameters being compared: lower layer temperature, smoke layer height, and neutral plane height.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.