Abstract
Porcelain electrical equipment is prone to brittle failure due to resonance under seismic effects. To improve its seismic resistance, some researchers have conducted research on shock absorption technology for porcelain electrical equipment. However, extant research fails to provide a detailed and systematic study of the effect of the nonlinear characteristics of these shock absorbers on the performance of equipment under seismic effects. This paper provides a theoretical analysis, verified by shaking table testing, of the performance of a 1000 kV pillar-type porcelain lightning arrester. The Bouc–Wen model is fitted to the force-displacement curve of hysteretic nonlinear metal shock absorbers, and a dynamic model of, and equations for, pillar-type porcelain electrical components are derived, taking into account their nonlinear characteristics. This reveals the influence of the nonlinear characteristics of shock absorbers on the nonlinear seismic response characteristics of these components. Our results indicate that the seismic responses of pillar-type porcelain components can be effectively suppressed by hysteretic nonlinear shock absorbers and that the greater the intensity of the seismic waves, the more obvious the efficiency of shock absorption. However, as the installation radius and yield force of the installed shock absorbers increase, their shock absorption efficiency gradually decreases.
Highlights
Research ArticleOn the Nonlinear Seismic Responses of Shock Absorber-Equipped Porcelain Electrical Components
As voltage classes have improved and the volume and mass of substation electrical equipment have been optimised, the increasing complexity of its structural systems has been paralleled by increases in its “height, size, flexibility, and weight” characteristics, exacerbating its seismic vulnerability and increasing risks of damage during earthquakes [1]. e natural frequency of pillar-type porcelain electrical components, especially ultra-high-voltage electrical equipment, is relatively low, mostly ranging from 1 to 2 Hz [2]
Conclusions is paper applies the Bouc–Wen model to fit restoring force-displacement curves for hysteretic nonlinear metal shock absorbers, avoiding the sharp inflection points introduced by bilinear models
Summary
On the Nonlinear Seismic Responses of Shock Absorber-Equipped Porcelain Electrical Components. Extant research fails to provide a detailed and systematic study of the effect of the nonlinear characteristics of these shock absorbers on the performance of equipment under seismic effects. Is paper provides a theoretical analysis, verified by shaking table testing, of the performance of a 1000 kV pillar-type porcelain lightning arrester. E Bouc–Wen model is fitted to the force-displacement curve of hysteretic nonlinear metal shock absorbers, and a dynamic model of, and equations for, pillar-type porcelain electrical components are derived, taking into account their nonlinear characteristics. Our results indicate that the seismic responses of pillar-type porcelain components can be effectively suppressed by hysteretic nonlinear shock absorbers and that the greater the intensity of the seismic waves, the more obvious the efficiency of shock absorption. As the installation radius and yield force of the installed shock absorbers increase, their shock absorption efficiency gradually decreases
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.