Abstract

This paper presents a simple iterative method for optimally sizing an inverter in a grid-connected photovoltaic (PV) system. Hourly solar radiation and ambient temperature data are used in this work for developing the models of grid-connected PV system. The results show that for the adapted case, the optimum inverter size ratio is 1.66 whereas the maximum efficiency reaches with this sizing ratio is 95.16%. Moreover, a comparison study is carried out between a conventionally sized inverter, with a capacity equals to the PV array capacity, and an optimized inverter. Based on that, the results show that the total energy produced from second case is higher than the first. Finally, the annual yield factor for optimum sizing system is higher than the conventionally sized system. This proves that the optimized PV inverter has better performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.