Abstract

Cyber attacks on the SCADA system can mislead the control center to produce incorrect state and topology estimate. If undetected, state and topology attacks can have detrimental impacts on the real-time operation of a power system. The problem of placing secure phasor measurement units (PMUs) to detect such attacks is considered. It is shown that any state or topology attack is detectable if and only if buses with secure PMUs form a vertex cover of the system topology. This condition leads to the countermeasures constructed by available graph algorithms. The examples with IEEE 14-bus, 118-bus, and 300-bus systems demonstrate applications of the countermeasures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.