Abstract

In this paper, the results of the energy efficiency and power loss measurements of a 16 kVA customer-end inverter (CEI) unit are analyzed. The CEI is part of the low-voltage dc (LVDC) distribution network. The efficiency of the CEI power conversion significantly affects the energy efficiency of the LVDC distribution network and the electricity supply chain. The efficiency of the CEI and its components is measured by applying calorimetric and electrical input-output methods. The power loss measurement results are analyzed, and the power loss mechanisms are described. The efficiency optimization goals are discussed and set.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.