Abstract

This paper describes an on-line PD (partial discharge) detection technique applicable to power cables. The method can be applied to both wire screen and solid shielded cables. In wire screen shielded cables, PD components with frequencies <100 MHz can be detected at distances over 150 m from the source, PD activity with levels as low as 20 pC can be detected within 100 m. However, in the case of solid shielded cables, PD levels of /spl ges/50 pC can be measured within 60 m in the frequency range <50 MHz. This method also can be utilized to check cable accessories such as splices and terminations. PD pulses with frequencies to /spl sim/300 MHz can be measured near the joints and terminations. The suitability and the sensitivity of the VHF technique were checked against two other alternative PD detecting techniques (pulse phase analyzer and high speed digital oscilloscope) by performing PD measurements in standard air gap and defects induced in EPR-insulated cable under laboratory-controlled conditions. The suitability and sensitivity of the VHF method were as good as the two alternative PD detection techniques.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.