Abstract

Modular multilevel converters (MMCs) are frequently featured to their modular structure, which results in fault-tolerant operation and easy redundancy realization. Nevertheless, in order to reach a given redundancy factor, more cells must be included in the converter, which directly affects the costs. This paper discusses the inherent redundancy of a modular multilevel converter (MMC) based static synchronous compensator (STATCOM) operating in the overmodulation region. Analytical expressions for the limits of the converter linear region were developed in order to define the minimum required dc-link voltage. Moreover, sensitivity analyses were implemented in order to show the effects of grid voltage variations, different output impedances, power factor and injected currents. The results indicated that the operation in overmodulation region has significant inherent redundancy. For a MMC based STATCOM with 26 cells, the converter can ride through 4 failures per arm without significantly increasing the output THD or reducing the injected current into the grid.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.