Abstract

In this paper, the authors analysed a cycling phenomenon in an actual control system. As a result of some experiments we came to the conclusion that this phenomenon was caused by a backlash element in the pneumatic controller. Carrying out the analysis of the control system including this nonlinear characteristic by the use of the gain-phase plane, it was found that the cycling frequency and amplitude were in good agreement with the experimental results. The larger the sensitivity of the proportional action controller is, the larger the frequency and the amplitude of the cycling.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.