Abstract
To quantify the non-linear variation of top-oil temperature with load current, and further investigate the key parameters in the thermal model, a model for calculating the oil exponent is proposed in this study. First, a global oil momentum model was established based on the fluid resistance characteristic. Then, based on the heat transfer coupling relationship between the winding, the oil flow, and the radiator (outside air), a set of control equations describing the oil temperature and the oil flow rate was established by using energy conservation. Simultaneously, the top-oil temperature was recorded from a field traction transformer to verify the physical part of the proposed model. The regression model parameters were identified with the ordinary least-square estimation so the oil exponent can be calculated naturally. The calculated oil exponent of the traction transformer at a wide range of load was 0.7308, so the accuracy was improved by 9.47% compared with the IEEE/IEC recommended value. Newly updated oil exponent was also verified through a dynamic overload heat run test. It is expected that the proposed oil exponent model can help in estimating top-oil temperature with more convenience and accuracy, especially in frequent overload conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.