Abstract
In this paper, the application of a recently invented power-synchronization control is proposed for integrating a doubly fed induction generator (DFIG)-based offshore wind farm to a weak ac grid through a voltage-source converter (VSC)-based high-voltage dc link. The control strategy, along with the antiwindup techniques and the bumpless transfer between two different control modes, is elaborately discussed. Two different fault cases, namely, onshore and offshore faults are considered and the fault-ride through techniques are presented. In case of the onshore fault, both with-chopper and without-chopper solutions are investigated. For an offshore fault, a coordinated fault-ridethrough scheme is proposed when the offshore HVDC converter and the wind farm are in voltage-control modes. The entire study is carried out in a real-time digital simulator (RTDS) platform.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.