Abstract

This paper proposes an offset voltage control scheme for the modular multilevel converter (MMC) operated in nearest level control (NLC) to improve the total harmonic distortion (THD) of AC phase voltages. Through the offset voltage control, the magnitude of each AC pole voltage maintains constant value with N+1 level in the range of whole modulation index (MI). The validity of the proposed scheme was confirmed by computer simulations for the MMC with 22.9kV/25MVA and experimental works for the scaled MMC with 380V/10kVA. It was confirmed that the proposed control scheme can generate constant pole voltages regardless the value of MI, and form phase voltages with improved THD.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.