Abstract

This paper describes an experimental investigation of the impact of structure geometry, fire location, and closed interior doors on occupant tenability in typical single family house geometries using common fuels from twenty-first century fires. Two houses were constructed inside a large fire facility; a one-story, 112 m2, 3-bedroom, 1-bathroom house with 8 total rooms, and a two-story 297 m2, 4-bedroom, 2.5-bathroom house with 12 total rooms. Seventeen experiments were conducted with varying fire locations. In all scenarios, two bedrooms had doors remaining open while the door remained closed in a third bedroom immediately adjacent to the open door bedrooms. Temperature and gas measurement at the approximate location of a crawling or crouching trapped occupant (0.9 m from the floor) were utilized with the ISO 13571 fractional effective dose (FED) methodology to characterize occupant tenability up to the point of firefighter intervention. The FED values for the fire room were higher for heat exposure than for toxic gases, while target rooms reached highest FED due to CO/CO2 exposure. The closed interior door decreased FED significantly, with the worst case scenario resulting in a 2% probability of receiving an incapacitating dose compared to the worst case scenario for an open bedroom of 93% probability of receiving an incapacitating dose. In fact, in 7 of the 17 experiments, the closed interior door resulted in a less than 0.1% chance of an occupant receiving an incapacitating dose prior to firefighter ‘intervention.’

Highlights

  • NFPA estimates that from 2009 to 2013 [1], U.S fire departments responded to an average of 357,000 residential fires annually

  • Calculations for fractional effective dose (FED) = 0.3 and total FED at firefighter intervention are provided in Tables 2 and 3 for the one-story structure and in Tables 4 and 5 for the two story structure

  • It is clear from these tables that at this point in the fire development, the additional threat from thermal exposure is typically less than the threat due to toxic gases, even in the fire rooms for the one-story structure

Read more

Summary

Introduction

NFPA estimates that from 2009 to 2013 [1], U.S fire departments responded to an average of 357,000 residential fires annually. These fires caused an estimated annual average of 2470 civilian deaths and 12,890 civilian injuries. While the average home size has increased by 71%, newer homes tend to incorporate features such as open floor plans and great rooms [3]. All of these features remove compartmentation and can contribute to rapid smoke and fire spread. While commercial building codes require fire and smoke separations to limit the impact of the fire on occupants, there are minimal requirements for compartmentation in single family homes [4]

Methods
Results
Discussion
Conclusion