Abstract

A load current sensorless control strategy using an optimized observer is designed for a three-phase online transformer-based UPS. A closed-loop observer containing state feedback is constructed based on the improved state space model of the inverter circuit. A simple feedback matrix design method is then applied to the observer according to the dead-beat control law, and the load current feedforward control scheme is reconstructed using the proposed observer. This control strategy can save three load current sensors, reduce the THD of the output voltage, and improve dynamic performance. The effectiveness of this strategy is verified by conducting simulation and experiment in a 10 kVA UPS.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.