Abstract
As the shape of water bridge retaining between vertical fins affects the performance of fin-and-tube heat exchangers, it is necessary to investigate water bridge shape and to develop description methods for water bridge, including those for contact line and contact angles. In this study, a visual experimental apparatus for observing the shapes of water bridges between vertical plane surfaces was designed, and the contact lines and the contact angles for water bridges on 7 types of plane surfaces made of aluminum, copper, stainless steel, quartz glass, acrylic plastics, Teflon and hydrophobic modified copper were measured. The test conditions cover water bridge volumes of 3–21 µL, and plane surface separations of 0.5–2.0 mm. The description method of water bridge shape is presented and compared with experimental data, including the description method of contact line with mean deviation of 2.2%, and the description method of contact angles with mean deviation of 6.1%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.