Abstract
This paper presents a robust and efficient algorithm for analyzing and restoring the observability of distribution grids. A linearized load flow model is used to characterize three-and multi-phase distribution grids under balanced and unbalanced conditions. Assuming that metering devices are installed to measure nodal magnitudes at some buses, the rank of the matrix associated with the non-metered magnitudes is determined by using a greedy strategy combined with a Gram-Schmidt orthonormalization procedure. Unlike other numerical-based techniques, the proposed algorithm avoids common errors caused by denominators close to zero. As an additional salient feature, a mathematically sound stopping criterion is provided to guarantee the robustness of the proposed algorithm. Furthermore, for unobservable grids, the algorithm identifies the linearly dependent rows in the aforementioned matrix, which correspond to the buses that should be metered to restore grid observability. The effective performance of the proposed algorithm is illustrated using several medium-and low-voltage benchmarks with up to 906 buses.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.