Abstract

This paper describes the behavior of an arc discharge in open air contaminated with metallic vapor between cathode and anode for kA-class high current using the numerical model. This simulation is related to a fundamental study on an arc discharge in high energy arcing fault (HEAF), which can be found occasionally in electric equipments like nuclear power plants. In this model, evaporation of metal cathode and anode, and metal vapor contamination to the arcs were taken into account. Using this model, the temperature, the pressure rise and the mass fraction of metal vapor in arc plasmas established between Fe electrodes were calculated for ac current of 15 kA peak in open air. The results show that arc temperature reached to more than 25000 K with 10wt% concentration of Fe vapor from electrodes in 15 kApeak arcs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.