Abstract
The EPRHR in the HPR1000 adopts natural circulation to meet the heat removal requirements of the containment for 72-hours under accident conditions. To reduce the evaporation depletion of water in CWT and enhances the passive cooling capability of the EPRHR, a long-term passive cooling scheme based on a heat pipe heat exchanger is proposed for CWT in this paper. Experimental study and numerical simulation are used to study the natural convection characteristics in the CWT. The results show that the scheme can take away 9 MW heat load as the average water temperature (Tave) is below 90 °C. The heat removal ability of the tube bundle is weakened row by row and the maximum difference of heat removal ability between tube bundles is 23%. The position of the tube bundles affects the Tave, and when the dimensionless layout factor (γ) = 3/4, Tave (346.34 K) is the smallest.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.