Abstract

Thermal comfort in a space equipped with a direct evaporative cooler is a function of the height of the cooler's supply air outlet. This article attempts to numerically investigate the impact of hybrid downdraft evaporative cooler (HDEC) supply outlet height on occupant thermal comfort in an office building. DesignBuilder CFD parametric simulations was carried out by varying the height of the HDEC supply outlet from 0.1m to 2.4 m, step 0.1 m above ground level, using Predictive Mean Vote (PMV) as an objective function. The results show that the best PMV of -0.27 was obtained at 0.4m above the floor level.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.