Abstract
More than 90% of the toxic gas in the industrial production process is heavy gas. However, under non-isothermal conditions, due to the uncertainty of the direction of buoyancy, the traditional ventilation method cannot be used to discharge heat and pollutants. In this study, we adopted the method of numerical simulation. The model used in this study is a two-dimensional double-diffusion model. The typical heavy-specific gravity gas sulphur hexafluoride (SF6) is used for the pollutants. When the buoyancy ratio is -1, the diffusion law of heavy gas pollutants under non-isothermal conditions is discussed. The results show that the temperature distribution and the pollutant distribution are mainly affected by the size of the vortex on the surface of the pollution source and the heat source. The temperature ventilation efficiency and the average Nu trend are similar, and put forward the optimal ventilation intensity relational formula in the square cavity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.