Abstract
This paper presents a numerical investigation of inlet air pre-cooling with water sprays to enhance the performance in Natural Draft Dry Cooling Towers (NDDCT). A 3-D numerical model of a test channel was generated and the evaporation from a single spray nozzle was analyzed. The droplet evaporation and the resulting cooling of air were predicted for a range of inlet air conditions and spray characteristics. The results showed that up to 81% evaporation can be achieved for water droplets of 20 μm at a velocity of 1 m/s and that, droplet transport and evaporation strongly depend on droplet size and air velocity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.