Abstract
Abstract In view of the present situation that the exhaust waste heat of the hot air hood in the paper drying section is too much and the environment is not friendly, a closed heat pump drying system model applied to the exhaust air hood is proposed and established. Effects of evaporation temperature and condensation temperature on supply air temperature, supply air moisture content, system performance coefficient (COP) and dehumidification energy consumption ratio (SMER) were studied. Results show that with the increase of condensation temperature, the supply air temperature is unchanged, and the moisture content of the supply air increase, while the COP and SMER of the system show a downward trend. The moisture content of supply air decrease with the increase of evaporation temperature, while the supply air temperature, COP and SMER all show an upward trend. Therefore, in order to improve the drying characteristics and improve the performance of the heat pump system, the condensation temperature can be reduced and the evaporation temperature can be increased.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.